What is Harmonics, Inter-harmonics, and Sub-harmonics ...???

What is Harmonics, Inter-harmonics, and Sub-harmonics ...???
Harmonics: A sinusoidal component of a periodic wave having a frequency that is an integer multiple of the fundamental frequency.

Inter-harmonics: Components with frequencies between two consecutive harmonics or those components whose frequencies are not integer multiples of the fundamental power frequency.

Sub-harmonics: A special subset of interharmonics that have frequency values that are less than that of the fundamental frequency.

Table below illustrate their usage with examples for a 50Hz system.

What is Crest Factor ...???

What is Crest Factor ...???

What is Crest Factor

The crest factor is the ratio of peak value to RMS value of waveform as shown in below figure. This ratio is also called to peak-to-RMS ratio. The crest factor is expressed as follows:
Crest Factor (peak-to-RMS ratio)= (peak value)/(RMS value)


For the power meter, crest factor has two meanings. One is a specification of the power meter itself. It expresses that the instrument has the capability of correct measurement how much distorted waveform. The other is the measuring of the crest factor of the input voltage or current of an input signal. It means to know quality of an input signal.

A measurement instrument specification

For a measuring instrument, the crest factor expresses the size of the dynamic range for an input signal. We define the crest factor as the size of dynamic range based on rated range value (RMS value).
For example, Crest factor of the WT2000 is three or six. It means possible to measure the input signal that peek value is three or six times larger than rated range value.
For example, using 100Vrms range and 1Arms range in the WT2000, available input voltage and current signals are as follows:
  • The case of select CF=3 in WT2000
  • The case of select CF=6 in WT2000


A measurement instrument specification

If input RMS value is lower than rated range value, the power meter can measure signal with more large crest factor. Below table shows between available input signal and the crest factor.
Input signal range which is defined accuracy, is within 10 to 110% of rated range. Therefore, in CF=3, the crest factor as the size of dynamic range for the WT series is up to 30 (at 10% of rated range value input) within the range of defined accuracy.
For your information, the WT series can display value when it puts the signal that is more than 0.5% of rated range value. If the input RMS value is 0.5% of rated range and input peek value is three times larger than rated range value, the crest factor becomes 600.
If an input exceeding the value shown in the specifications is measured, the peak area of the waveform is clipped to cause an error.

Quality of an input signal

Below table shows RMS value, crest factor and form factor for a typical waveform. The form factor is defined as RMS value/MEAN value. The crest factor of sine wave is the square root of 2.
If it calculates crest factor of input signal and compares this crest factor with the square root of 2, it knows how much distortion ratio of input waveform.
Below figure shows thyristor waveform characteristic for firing angle versus crest factor.

Below figure shows pulse waveform characteristic of pulse duty cycle (=t/T) versus crest factor.


SOURCE : http://www.yokogawa.com/ymi/tutorial/tm-tutorial_wt_08.htm

Let a look at this "Harmonic filtering"

Let a look at this "Harmonic filtering"
In cases where the preventive action presented above is insufficient, it is necessary to equip the installation with filtering systems.
There are three types of filters:
  • Passive
  • Active
  • Hybrid

Passive filters

Typical applications

  • Industrial installations with a set of non-linear loads representing more than 500 kVA (variable-speed drives, UPSs, rectifiers, etc.)
  • Installations requiring power-factor correction
  • Installations where voltage distortion must be reduced to avoid disturbing sensitive loads
  • Installations where current distortion must be reduced to avoid overloads

Operating principle

An LC circuit, tuned to each harmonic order to be filtered, is installed in parallel with the non-linear load (see Fig. M28). This bypass circuit absorbs the harmonics, thus avoiding their flow in the distribution network.
Generally speaking, the passive filter is tuned to a harmonic order close to the order to be eliminated. Several parallel-connected branches of filters can be used if a significant reduction in the distortion of a number of harmonic orders is required.
FigM20.jpg
Fig. M28: Operating principle of a passive filter

Active filters (active harmonic conditioner)

Typical applications

  • Commercial installations with a set of non-linear loads representing less than 500 kVA (variable-speed drives, UPSs, office equipment, etc.)
  • Installations where current distortion must be reduced to avoid overloads.

Operating principle

These systems, comprising power electronics and installed in series or parallel with the non-linear load, compensate the harmonic current or voltage drawn by the load.
Figure M29 shows a parallel-connected active harmonic conditioner (AHC) compensating the harmonic current (Ihar = -Iact).
The AHC injects in opposite phase the harmonics drawn by the non-linear load, such that the line current Is remains sinusoidal.
FigM21.jpg
Fig. M29: Operating principle of an active filter

Hybrid filters

Typical applications

Industrial installations with a set of non-linear loads representing more than 500 kVA (variable-speed drives, UPSs, rectifiers, etc.)
  • Installations requiring power-factor correction
  • Installations where voltage distortion must be reduced to avoid disturbing sensitive loads
  • Installations where current distortion must be reduced to avoid overloads
  • Installations where strict limits on harmonic emissions must be met

Operating principle

Passive and active filters are combined in a single system to constitute a hybrid filter (see Fig. M30). This new filtering solution offers the advantages of both types of filters and covers a wide range of power and performance levels.
FigM22.jpg
Fig. M30: Operating principle of a hybrid filter

Selection criteria

Passive filter

It offers both power-factor correction and high current-filtering capacity.Passive filters also reduce the harmonic voltages in installations where the supply voltage is disturbed. If the level of reactive power supplied is high, it is advised to turn off the passive filter at times when the percent load is low.
Preliminary studies for a filter must take into account the possible presence of a power factor correction capacitor bank which may have to be eliminated.
Fig M31.jpg
Fig. M31 : Example of MV passive filter equipment

Active harmonic conditioners

They filter harmonics over a wide range of frequencies and can adapt to any type of load. On the other hand, power ratings are limited.
Fig M32.jpg
Fig. M32 : Active Harmonic Conditionner (AccuSine range)

Hybrid filters

They combine the performance of both active and passive filters.
Fig M33.jpg
Fig. M33 : Example of hybrid filter equipment